The Netherlands is standardising smart heating. The harder task is coordinating thousands of independently controlled devices within the limits of the electricity grid.
Quick Take
From 2028, participating Dutch manufacturers will produce heat pumps capable of smart control. A pilot in Dalen shows how collective control can reduce evening peaks, but reliable grid flexibility requires more than connected appliances. Local capacity signals, household preferences, coordinated energy management and measured outcomes must work together, including during cold weather and the recovery period after an intervention.
Imagine an entire neighbourhood equipped with intelligent heat pumps, dynamic electricity tariffs and automated home energy management systems. Every household optimises its energy consumption, every device communicates correctly, and every manufacturer complies with the relevant technical standards.
The neighbourhood transformer could still be overloaded. There need not be anything wrong with the individual devices. They may simply be responding to the same incentives at the same time, without knowing how much capacity is available in their street.
On 5 November 2026, Dutch heat-pump manufacturers, grid operators and TNO announced an agreement: from 2028, newly produced heat pumps from participating manufacturers will be technically capable of smart control. Making a heat pump controllable is an engineering achievement. Coordinating thousands of them within the limits of the electricity grid is a different challenge.
What the Dutch agreement actually delivers
The agreement builds on NTA 8171, the technical agreement published by NEN in October 2026. It addresses communication and control across the heat-pump installation, providing a common basis for manufacturers and other parties. The sector agreement also explicitly assigns grid operators responsibility for the necessary signals and conditions. It would be unfair to suggest that the industry has overlooked the coordination problem; the question is how those commitments will work in practice.
There is a separate government proposal for 2029: smart hybrid heat pumps would become the norm when replacing gas boilers in homes outside district-heating plans. Its implementation is still being worked out. Neither the proposal nor the manufacturing agreement means that all installed heat pumps will automatically become a dependable source of flexibility.
What a hundred heat pumps in Dalen actually proved
There is already a useful Dutch example. In Dalen, Drenthe, the DACS-HW consortium, including Enexis, Intergas and Eindhoven University of Technology, tested collective control of approximately one hundred hybrid heat pumps connected behind the same neighbourhood transformer. Enexis reported a 10–25% reduction in the evening peak under the conditions of the trial, with roughly 40% of households participating. Residents could override the control through a comfort button.
The public final report is particularly informative. The transformer had a nominal rating of 400 kVA and served 255 homes. That rating was not exceeded during the project. The team tested different control scenarios, including dynamic operation based on grid measurements and forecasts. The hybrid installations also had the option of using their gas boilers to maintain heating. These qualifications matter: a reduction in an experimental peak is not evidence that every neighbourhood can avoid reinforcement, and a hybrid system has an alternative heat source that a fully electric system does not necessarily have.
The achievement in Dalen was the coordination of the devices and the local network. The next question is how to make that arrangement repeatable across different neighbourhoods, manufacturers, energy contracts and types of heating installation.
A cheap hour is not necessarily a quiet street
A home energy manager may sensibly schedule heating for a period of inexpensive electricity. If the low price coincides with spare local grid capacity, everyone benefits. But wholesale electricity prices cannot establish the capacity available at a particular distribution transformer. Where many households follow the same price signal, consumption may become more synchronised. The resulting peak depends on the local load, device diversity and the timing of the other demands.
The 2026 Flexibility Needs Assessment, prepared by the Dutch grid operators and assessed by ACM, distinguishes balancing the electricity system from relieving network congestion. Its assumptions about future flexibility also carry uncertainty. Household price optimisation and local network operation are legitimate but different objectives. The operating rules need to explain what happens when they conflict.
The coldest evening is the interesting test
Consider a cold, windless winter afternoon. Residents return home, heating demand increases, cars are plugged in and cooking begins. This is one plausible stress scenario, not a description of every Dutch congestion event. The relevant question is how much electrical demand can be deferred at that moment without compromising heating, domestic hot water or subsequent recovery.
It would be equally wrong to assume that heat pumps have no flexibility left when it is cold. A 2026 study in Energy analysed operating data from up to 761 air-to-water heat pumps in southern Germany. Even during the cold spells studied, the devices showed headroom for load shifting. This is useful evidence of potential, although the dataset cannot establish the amount of flexibility that can reliably be offered on any particular Dutch feeder.
Thermal storage offers options, but the duration matters. Experimental work reported by Pacific Northwest National Laboratory supports the feasibility of demand limiting and preheating under tested conditions. A 2025 field experiment near Ghent provides a useful caution: nine heat pumps were subjected to 287 interventions, about 19% of which were overridden by residents. Recovery consumption eroded some of the initial reduction. A small study of well-insulated homes cannot predict national results, but it explains why evaluating only the intervention window can give a misleading impression of success.
To illustrate the coordination problem, consider 200 households, of which 100 have individually controlled heat pumps. The combined load also includes EV charging and ordinary household consumption. Assume a local operational limit of 250 kW of active power, rather than a single domestic connection or the transformer’s nominal kVA rating. In this illustrative 24-hour profile, uncontrolled demand reaches 300 kW in the 17:00–18:00 interval. An intervention from 15:00 to 17:00 followed by simultaneous recovery makes the peak worse, at 315 kW. Preheating and staggered recovery can instead hold the peak at 240 kW, 20% below the uncontrolled case. Each scenario consumes exactly 4,199 kWh over the day; 130 kWh is shifted in the coordinated case. These are synthetic hourly mean values, not measurements from Dalen. Actual energy use and heating efficiency may vary with the control strategy.
Who is actually in charge?
A practical architecture needs to coordinate the grid operator, energy supplier, flexibility service provider and household. The grid operator is best placed to identify the relevant network constraint; the supplier or tariff service provides the commercial price signal. A flexibility service provider can aggregate available reductions under the applicable contracts, while a home energy management system (HEMS), where installed, can coordinate heating, EV charging and other controllable devices behind the household’s meter. The heat-pump controller retains responsibility for equipment protection and permitted operating limits. The resident sets comfort preferences and the terms of participation.
This is a proposed division of responsibilities, not a claim that every party already has the necessary contractual authority or data access. A central service can coordinate many households, as Dalen illustrates, while local controls continue to protect the installation and respect the resident’s choices. There is no need to turn every living room into a remotely operated control room.
Consider a hybrid heat pump scheduled to reduce electrical demand in response to a local constraint. Switching to gas may protect comfort, but can change the household’s energy costs and emissions relative to the planned operation. The commercial arrangement must therefore address who bears those costs and how the benefit of providing flexibility is shared. Without a clear incentive, dependable participation cannot simply be assumed.
The architecture also needs an agreed fallback. A lost internet connection should not disable safe heating. Permissions, secure software updates, time-limited requests and explicit recovery behaviour are part of the operating design. These responsibilities become even more important when several services are requesting flexibility from the same household.
What should the sector demonstrate before 2028?
By 2028, manufacturers should be able to demonstrate that their heat pumps respond correctly to external signals. That is a useful technical objective. The energy sector needs a different acceptance test: can a neighbourhood remain within a relevant local network limit on a cold evening, while respecting household comfort, accounting for any additional energy costs and avoiding a new peak when heating resumes?
A convincing trial should measure actual network loading against a suitable baseline, the availability and delivery of requested flexibility, resident overrides, recovery demand and the consequences for energy costs. It should compare price-driven operation with locally coordinated operation and test failures of communication as well as successful interventions. Where flexibility cannot meet the network’s requirements at an acceptable cost, reinforcement remains a legitimate option.
Dalen gives the sector a useful starting point. Repeating that achievement at scale requires a shared operating model, clear responsibilities and performance evidence that covers the whole cycle, from the initial request to the return to normal heating. The transformer, after all, has very little interest in how smart the individual appliances claim to be.
For further reading on the practical coordination problem, see Energy Management Has a Terrible User Experience Problem and Smart Grid Strategy: Turn Energy Data Into Decisions.